MODEL |
SYM600/50X |
SYM500/50X |
SYM400/50X |
SYM300/50X |
SYM200/50X |
SYM100/50X |
SYM240/40X |
SYM160/40X |
SYM80/40X |
System Capacity |
600kVA |
500kVA |
400kVA |
300kVA |
200kVA |
100kVA |
240kVA |
160kVA |
80kVA |
Power Module Capacity |
50 kVA/50 kW |
40 kVA/40 kW |
Input |
Dual Input |
Standard |
Phase |
3 Phase + Neutral + Ground, 380V/400V/415V (line-line) |
Input Voltage Range |
304 ~ 478V ac (line-line) fullload;
228V ~ 304ac (line-line) load decreases linearly according to the min phase voltage |
Rate Frequency |
50/60Hz |
Input Frequency Range |
40Hz ~ 70Hz |
Input PF |
>0.99 |
Input THDi |
<3%(100% Linear load) |
Bypass |
Rate Voltage |
380/400/415Vac (line-line) |
Rate Frequency |
50/60Hz |
Input Voltage Range |
Settable, -40% ~ +25% |
Bypass Frequency Range |
Settable, ±1Hz, +3Hz, ±5Hz |
Bypass Overload |
110% Long term operation
110%~125% last for more than 5min
125%~150% last for more than 1min
>150% last for more than 1s |
125%, long time
<130%, for 10 mins
<150%, for 1 min
>150%, for 300ms |
110% long time
125% for 5mins
150% for 1 min
>150% for 1s |
125% long time
130% for 10 minutes
150% for 1 min
>150% for 300ms |
Output |
Rate Voltage |
380/400/415Vac (line-line) |
Voltage Regulation |
1% for balance load; 1.5% for unbalance load |
Rate Frequency |
50/60Hz |
Frequency Precision |
0.1% |
Output PF |
1 |
Output THDu |
<1%, Linear load; <5.5%, Non-linear load |
Crest Factor |
3:1 |
Inverter Overload |
<110% for 1 hour; 125% for 10 mins; 150% for 1 min; >150% for 200 ms |
Batterie |
Voltage |
±240Vdc |
Battery Number |
40pcs (Settable: even number from 32 to 44) |
Voltage Precision |
1% |
Charge Power |
up to 20% Output active power |
Battery Cold Start |
Standard |
Optional |
Standard |
Optional |
Efficiency |
AC Mode |
95% |
ECO Mode |
99% |
Battery Mode |
95% |
System |
Display |
10.4" (240-600kVA) or 7" (80-200kVA) touch screen LCD + LED+ Keyboard |
IP Class |
IP 20 |
Interface |
RS232, RS485, Programmable Dry Contact |
Option |
SNMP Card, Parallel kit, SPD, LBS, Dust filter |
Temperature |
Operation:0 ~ 40°C Storge: -40 ~ 70 °C |
Relative Humidity |
0 ~ 95% Non-condensing |
Physical |
Altitude |
<1000m. Load derated 1% per 100m From 1000 ~ 2000m |
Noise (1 meter) |
72dB @ 100% load, 69dB @ 45% load |
Applicable Standards |
Safety: IEC/EN 62040-1 EMC:IEC/EN 62040-2 Performance: IEC/EN 62040-3 |
Weight (kg) |
Cabinet |
1040 |
900 |
700 |
490 |
350 |
210 |
490 |
350 |
210 |
Power module |
45 |
44 |
Dimension
W*D*H(mm) |
Cabinet |
1300*1100*2000 |
1050*1100*2000 |
650*1095*2000 |
650*960*1600 |
600*980*1150 |
650*1095*2000 |
650*960*1600 |
600*980*1150 |
Power module |
510*700*178 |