Solar Input |
Voltage |
85-440Vdc (Normal: 220Vdc) |
MPPT Efficiency |
>99% |
Input Current |
<15Arms at 220Vdc input; <19Arms at 176Vdc input |
DC Output |
Voltage |
42-58Vdc (Normal: 53.5Vdc) (HVDC CB must configed for each module) |
Solar Power |
600A (Max. 12*SP II Solar Convertor 48/3000HE) |
Max. Current |
62.5A at 48Vdc |
Static voltage regulation |
<0.5% |
Dynamic Voltage regulation |
<5% for 10% - 90% load, regulation time <50ms |
Ripple |
<150mV peak to peak |
Psophometric |
<2mV |
Hold-up Time |
>10ms |
Startup Time |
3-8s |
Energy Management |
Controller |
Energy Management |
Configurable, depend on the OPEX saving targets |
Battery Management |
Lead-acid battery and Lithium battery, Mid-point monitoring |
Hybrid Energy Support |
PV, Grid, Genset, Battery |
Physical |
RS485, Ethernet, CAN, USB |
Protocol |
Http, Modbus, IPV4, SNMPV1/V2c |
ManaApplicable Standardsgement |
Safety |
IEC60950-1, UL60950-1, EN60950-1 |
EMC |
EN55022ClassB
IEC61000-3(-2,-3)
IEC61000-4(-2,-3,-4,-5,-6,-8,-11) |
Environment |
ETSIEN300019-2(-1,-2,-3); ETSIEN300132-2
Tecordia, NEBS, GR63, CORE, Zone4, ROHS |
Other |
Typical Load |
<5KW |
Temperature |
Operating: -40°C ~ +75°C; Storage:-40°C ~ +85℃ |
Humidity |
Operating:≤95% non-condensing;
Storage: ≤99% non-condensing |
Altitude |
4000m |
Acoustic Noise |
55dB |
Input Protection |
6KA lightning protection |
Output Protection |
59Vdc Over voltage shutdown; Short circuit proof Output fuse |
lsolation |
3.0KVac - lnput and output; 1.5KVac - Input and earth; 0.5KVac - Output and earth |