Series |
Conventional Air Conditioning Version |
System |
Index |
EC20 |
ER02 |
ER03 |
ER05 |
Power supply and
distribution |
UPS Capacity |
3KVA |
6KVA |
10KVA |
20KVA |
Power factor |
0.8 |
0.8 |
0.8 |
0.9 |
Total power input |
220V/40A |
220V/63A |
220V/125A |
380V/125A |
Height |
4U |
4U |
4U |
6U |
Lightning protection |
C class |
Others |
ATSModle(optional) |
Cabinet |
Recommended number of IT cabinets |
1 |
2 |
3 |
5 |
Available space |
28U |
33U+42U |
29U+2*42U |
30U+4*42U |
Number of PDUs in a single rack |
1*8bit10A |
1*12bit10A |
1*(12bit10A+4bit16A) |
Closed aisle |
Fully enclosed cold and hot aisle |
Ergency ventilation |
Fan-type emergency ventilation system, support maximum 5KW heat dissipation, automatic start and stop |
IT space expansion |
Standard IT cabinet with 42U usable space (optional) |
Refrigiration |
Type |
Rack mount |
In row |
In row |
In row |
Cooling Capacity (KW) |
3.5 |
7.5 |
12.5 |
2*12.5 |
Sensible heat ratio |
1 |
System |
Compression system +EC fan |
Monitoring |
Monitoring volume |
UPS、Power distribution、AC、Water leakage、Temperature & Humidity、Smoke、Door sensor |
Function |
Data collection and storage, alarm management, energy consumption analysis, remote access, sound andlight alarm (optional), SMS alarm (optional), APP (optional) |
Display |
10-inch Touch screen |
Fire |
Heptafluoropropane |
1URack-mounted gas fire extinguishing system (optional) |
Batterie |
Standard number of batteries |
8 |
16 |
16 |
20 |
Backup power for 15 minutes |
2UBattery Pack |
3UBattery Pack |
—— |
6UBattery Pack |
Backup power for 40 minutes |
—— |
—— |
—— |
External 20 100A/12V |
Backup power for 90 minutes |
—— |
—— |
—— |
—— |
Longer time delay |
Can be replaced with high-capacity batteries or increase the number of battery packs (not more than 4) |
Size |
W*D*H-mm |
600*1200*2000 |
1500*1200*2000 |
2100*1200*2000 |
3600*1200*2000 |
Environment |
Environment temperature |
0~45℃ |
Environment humidity |
Relative humidity 0-95%, no condensation |
Altitude |
<1000m,The excess part is derated according to relevant standards |