Power Factor: 0.9 ; 208/220/230/240Vac
Overviews
Standard size, easy to install and replace; Can be developed to a higher place, reducing floor space; Can be paralleled/expanded (renewable order); Static switch, zero switching; Large capacity, high precision, parallelable; Online double conversion structure design, providing continuous clean power, protecting key electrical equipment from power outages, power instability, frequency drift, harmonic interference, etc. High efficiency, high input and output power factor, fully matching modern IT load equipment, energy saving and environmental protection, and bringing additional benefits to customers.
  • Features

  • Specifications

  • Applications

  • Télécharger

True double-conversion

Microprocessor control optimizes reliability

Input power factor correction

Output power factor 0.9

Wide input voltage range

Converter mode available

ECO mode for energy saving only available for 1-3K models

Generator compatible

Adjustable charging current via LCD or software (1A~6A)

Emergency power offfunction (EPO) only available for 6K/10K models

Comprehensive display allows easy monitoring and access of UPS status

Read More
MODEL SYRT WinnerPro+1kVA SYRT WinnerPro+2kVA SYRT WinnerPro+3kVA SYRT WinnerPro+6kVA SYRT WinnerPro+10kVA
PHASE  Single phase with ground
CAPACITY* 1000 VA/900W 2000 VA/ 1800W 3000 VA/2700 W 6000VA/5400W 10000 VA/9000W
INPUT
 Nominal Voltage 110/115/120/127VAC or 208/220/230/240VAC 208/220/230/240VAC
 Input Voltage Range 60-145 VAC or 120-300 VAC (Based on load at 50%)
90-145 VAC or 180-300 VAC (Based on load at 100%)
110-300 VAC (Based on load at 50%).
176-300 VAC (Based on load at 100%)
 Frequency Range 40 Hz ~ 70 Hz 46~54 Hz or 56~64 Hz
 Power Factor ≧0.99 @ Nominall Voltage (100% load)
OUTPUT
 Output Voltage 110/115/120/127VAC or 208/220/230/240VAC 208/220/230/240VAC
 Voltage Regulation ±1%
 Frequency Range(Synchronized Range) 47~ 53 Hz or 57 ~63 Hz 46Hz~54 Hz or 56Hz~64 Hz
 Frequency Range(Batt. Mode) 50 Hz or 60Hz±0.5% 50 Hz±0.1 Hz or 60 Hz±0.1 Hz
 Current Crest Ratio 3:1
 Harmonic Distortion ≦3%THD(Linear Load)
≦6% THD(Non-linear Load)
≦3 %THD (Linear Load)
≦5 % THD(Non-linear Load)
 Transfer
 Time
AC Mode to Battery Mode  Zero 0 ms
 Inverter to Bypass 4m s (Typical) 0 ms
 Waveform(Batt. Mode)  Pure Sinewave
EFFICIENCY
AC Mode 88% 89% 90% 92% 93%
 Battery Mode 83% 87% 88% 90% 91%
BATTERY
 Standard
 unit
 Battery Type 12V/9Ah 12V/9Ah 12 V/9Ah 12 V/9Ah
 Numbers 2 3 4 6 16 20 16 20
 Typical Recharge Time 4 hours reco ver to 90% capacity 9 hours reco ver to 90% capacity
 Charging Current(max.) 1A 1A/2A(Adjustable)
 Charging Voltage 27.4VDC±1% 41.0VDC±1% 54.7 VDC±1% 82.1 VDC ±1% 218.4 VDC±1% 273VDC ±1% 218.4 VDC±1% 273VDC±1%
 Long backup
 unit
 Battery Type  Depending on applications
 Numbers 3 6 6 16~ 20 (Adjustable)
 Charging Current(max.) 1.0A/2.0A/4.0A/6.0 A 1A/2A/4A/6A(Adjustable,6Ais only available for 16 pcs batteries)
 Charging Voltage 41.0VDC±1% 82.1 VDC±1% 82.1VDC±1% 218.4 VDC±1%(Based on 16 pcs batteries)
INDICATORS
LCD  Load level, Battery level,AC mode, Battery mode, Bypass mode, and Fault indicators
ALARM
 Battery Mode  Sounding every 4 seconds
 Low Battery  Sounding every second
 Overload  Sounding twice every second
 Fault  Continuously sounding
PHYSICAL
 Standard
 unit
 Dimension,DxWxH (mm) 310×438
×88
410×438×88 630×438×88 UPS Unit:
500×438×88[2U]
 Battery Pack:
668x438x88[2U]
UPS Unit:
500x438x88[2U]
 Battery Pack:
580x438x133[3U]
UPS Unit:
580×438×133[3U]
 Battery Pack:
580x438x133[3U]
 Net Weight(kgs) 12 14.1 19 29.3 UPS Unit:15
 Battery Pack:48
UPS Unit:15
 Battery Pack: 61
UPS Unit: 18
 Battery Pack:51
UPS Unit :18
 Battery Pack: 61
 Long backup
 unit
 Dimension,DxWxH (mm) 310×438×88 410×438×88 460×438×88 500×438 ×88[2U] 580×438×133[3U]
 Net Weight(kgs) 9 12 14.2 15 18
ENVIRONMENT
 Humidity 20-90% RH @0 - 40℃ (Non-condensing) 0-95% RH @0-40°C(non-condensing)
 Noise Level  Less than 50dB @ 1 Meter  Less than 55dB @ 1 Meter  Less than 58dB @ 1 Meter
MANAGEMENT
 Smart RS-232/USB  Supports Windows®2000/2003/XP/ Vista/2008,Windows®7/8/10, Linux and MAC
 Optional SNMP  Power management from SNMP manager and web browser

• 1-3KVA: Derate to 70% of capacity in Frequency converter mode or when the output voltage is adjusted to 208VAC;
6-10KVA: Derate to 60% of capacity in Frequency converter mode and to 90% when the output voltage is adjusted to 208VAC.
• Long backup unit is only available in 208/220/230/240VAC systems;
Product specifications are subject to change without further notice.