MaisonProduitsAlimentation UPSOnduleur haute fréquenceTower 3-Phase 10-200kVA High Frequency UPS
  • High-Frequency-UPS-Tower-10-to-200kva
  • High-Frequency-UPS-Tower-10-to-200kva

Tower 3-Phase 10-200kVA High Frequency UPS

Power Factor: 1 & 0.9 ; 110V - 300V ;
Overviews
Tower UPS combines powerful performance, advanced technology, reliable operation, efficient monitoring, and flexible design. It is an ideal choice for safeguarding critical power - dependent systems and ensuring uninterrupted operation in diverse and demanding applications.
  • Features

  • Specifications

  • Applications

  • Télécharger

Double conversion online topology design.
Supports parallel function.
Ultra-wide mains input range (110V – 300V).
Input power factor correction function.
Output power factor up to 0.9 and 1.
LCD display.
With emergency power off (EPO) function.
With SNMP + USB + RS-232 multi-monitoring functions.
Optional intelligent battery monitoring module.

Read More
Model/HF33 10KVA 15KVA 20KVA 30KVA 40KVA 60KVA 80KVA 100KVA 120KVA 160KVA 200KVA
Phase 3-phase 4-wire input/3-phase 4-wire output
Capacity 10KVA 10KW 15KVA 15KW 20KVA 20KW 30KVA 30KW 40KVA 40KW 60KVA 60KW 80KVA 80KW 100KVA 90KW 120KVA 108KW 160KVA 144KW 200KVA 180KW
Parallel capability 4 2
Enter
Rated voltage 3x380VAC (3ph+N+PE)
Voltage range 110-300VAC@50% load; 176-276 VAC @ load  
Frequency range 40 ~ 70HZ 40~70Hz
Power factor ≥0.99@100% load ≥0.99@100% load
Harmonic Distortion (THDi) Linear load<3% Linear load<3%
Output
Rated voltage 3x360*/380/400/415 VAC(3PH+N) 3x380/400/415VAC(3PH+N)
Output accuracy (battery mode) ±1% ±1%
Frequency range (synchronous correction range) 46 ~ 54Hz or 56 ~ 64Hz 46 ~ 54Hz or 56 ~ 64Hz
Frequency range (battery mode) 50/60Hz±1% 50Hz±0.1Hz or 60Hz±0.1Hz
Current peak ratio 3:1 (maximum) 3:1 (maximum)
Harmonic Distortion (THDv) ≦1 %THD (linear load); ≦3%THD (non-linear load) 3:1 (maximum)
Conversion time Mains mode to battery mode none ≤2%THD (linear load);≤4%THD
Inverter to bypass none none
Waveform (battery mode) pure sine wave pure sine wave
Overload capacity 1100-110%60 minutes·111-125%10 minutes·126%-150%1 minute; >150%400ms 105-110% effect for 1 hour·111-125% effect for 10 minutes·126-150% effect for 1 minute·>150% effect for 200ms
Bypass
Rated voltage 3x380/400/415VAC(3PH+N) 3×380/400/415VAC(3PH+N)
Voltage range -30%~+20% (adjustable) -30%~+20%
Frequency range (synchronous correction range) 46 ~ 54Hz or 56 ~ 64Hz +/-1Hz·+/-2Hz·+/-4Hz (Default: 4Hz)
Overload capacity >130% for 1 minute (default), continuous operation until circuit breaker protection (optional) 105-110%60 minutes·111-125%10 minutes126-150%1 minute·>150%200ms
Efficiency
Mains power mode 96% 94%
ECO mode 99% 98%
Battery mode 96% 93%
Batterie
Standard machine Battery Type 12V/9Ah 12V/9Ah 12V/9Ah 12V/7AH 12V/9Ah Not supported Not supported
Quantity (10+10) (16+16) (16+16) (16+16)x2 (16+16)x2
Charging Capacity 9 hours to restore to 90% capacity
Maximum charging current 1A~12A (adjustable) 1A~16A (adjustable)
Charging voltage ±136.5VDC ±218VDC
Long-acting machine Battery Type Match multiple battery boxes according to actual application
Quantity 16~32 (optional) 32~40 (optional) 20~32 (optional) 32~40 (optional) 32~40 (adjustable)
Maximum charging current 1A~12A(adjustable) 1A~16A(adjustable) 2A~32A(adjustable) 24A 32A 40A 48A
Charging voltage ±13.65V×number of batteries (number of batteries = 16~20) ±13.7Vx number of batteries (number of batteries = 16~20)
Display instructions
LCD Display UPS status, load capacity, battery capacity, input/output voltage, discharge time and fault indication 10-inch touch color LCD display
Physical properties
Standard machine Dimensions, depth x width x height (mm) 630×250×827 815×300×1000 Not supported
Net weight (kg) 93 125 225 250
Long-acting machine Dimensions, depth x width x height (mm) 630×250×827 815×300×1000 790×360×1010 940×567×1015 1040×567×1452
Net weight (kg) 37 40 65 67 110 116 199 234 306 340  
Usage Environment
Temperature and humidity 0-40°C; 0-95% relative humidity (non-condensing)
Altitude** 0 ~ 1500m when fully loaded
Noise Less than 60dB@1m Less than 63dB@1m Less than 65dB@1m Less than 70dB@1m Less than 73dB@1m
Control Management
Intelligent RS-232/USB Supports Windows°2000/2003/XP/ Vista/2008, Windows° 7/8, Linux and MAC
Optional SNMP Power management supports SNMP management and network management

*When the output voltage is set to 3×360VAC, the output is derated to 90%. **If the UPS is installed or used at an altitude higher than the maximum altitude, the output power is reduced by 1% for every 100m. Product specifications are subject to change without prior notice