Hot & Cold Aisles Modular Containment Data Center

Single row 3-24 ; Double row 6-48
Overviews
The MC6000 series intelligent micro-module data center is the latest-generation data center infrastructure solution. It integrates all traditional data center subsystems like cabinets, cooling, power distribution, etc. into one product.
It uses high-efficiency, reliable modular precision power distribution equipment. With a standardized architecture, components have high commonality. All are pre-fabricated in the factory, shortening construction time and facilitating maintenance. It's highly reliable and secure, allowing for quick and flexible system deployment and relocation.
The micro-module offers three modes: closed cold aisle, closed hot aisle, and closed cold and hot aisles. Aisle doors come in rotating sliding, automatic sliding, and manual sliding styles to meet different customer needs.
  • Features

  • Specifications

  • Applications

  • Download

Reliability
• Standardized system architecture design with high-commonality components, avoiding system design issues.
• Fault-tolerant system design for high reliability.
• Separation of strong and weak currents to reduce electromagnetic interference.
• Supports early-stage (optional) fire warning.
• Passed seismic performance tests with power on at intensity levels 8 and 9.

Efficiency
• High-efficiency integrated power distribution and closed cold and hot aisles, leading in power density and energy efficiency in the industry.
• Supports various configurations of single-row or double-row enclosed cold and hot aisles to isolate cold and hot airflows and eliminate local hot spots.

Simplicity
• Adopts a standard modular architecture design, enabling modular combinations of different sizes and powers. Product delivery can be completed in 3-6 weeks.

Intelligence
• The micro-module monitoring system comprehensively monitors and centrally manages equipment such as power distribution, environment, security, and fire protection within the micro-module.
• Precise energy consumption analysis of the micro-module is carried out through the precision power distribution system.

Energy-saving
• Through the enclosed-aisle design, the PUE can be maintained at a relatively low level, making it more energy-efficient than traditional machine rooms.
• Allows for later expansion. Expansion and upgrades can be carried out gradually according to future development, saving initial investment costs.

Read More
Project Specification
Micro-module system Dimensions Single row sealed cold/hot aisle (LxW×H)
Lx2465x2550/2750mm, L≤15m, height 2550/2750mm is the total height of the system after the skylight is flipped
Lx2365x2550/2750mm, L≤15m, height 2550/2750mm is the total height of the system after the skylight is flipped
Lx2265x2550/2750mm, L≤15m, height 2550/2750mm is the total height of the system after the skylight is flipped
Double row sealed cold/hot aisle (LxW×H)
Lx3600x2550/2750mm, L≤15m, height 2550/2750mm is the total height of the system after the skylight is flipped
Lx3400x2550/2750mm, L≤15m, height 2550/2750mm is the total height of the system after the skylight is flipped
Lx3200x2550/2750mm, L≤15m, height 2550/2750mm is the total height of the system after the skylight is turned
Passage Door Rotating sliding door (hidden door closer and hidden electromagnetic lock design improve the aesthetics of the product, and the dynamic environment monitoring display can be installed inside or outside the channel)
Sliding door (optional automatic/manual, with 200mm deep cabinets on both sides, can hide the sliding door, can install dynamic environment equipment)
Number of single module cabinets Single row 3-24; Double row 6-48
Power supply type AC:380/400/415Vac, 50/60Hz, 3Ph+N+PE
DC:-48/240/336Vdc, positive and negative +PE
Single module IT power consumption Maximum support 200kW (more than 200kW need to confirm with the engineer)
Maximum power per cabinet 18kW
Work Environment Ultra-low temperature working conditions: -40~45℃
T1 working condition: -25~45℃
T3 working condition: -5~45℃
Reliability level Tier Il or Tier IIl (expandable to Tier IV)
altitude If the distance exceeds 1000m, the rating needs to be reduced.
Cabinet Dimensions (W*D*H) 600/800×1200×2000/2200mm
600/800×1100×2000/2200mm
600/800×1000×2000/2200mm
Available space 42U/47U
IP Rating IP20
Air-cooled row air conditioner Cooling capacity (single air conditioner) 12kW/25kW/40kW
Internal size 300/600×1000/1100/1200×2000/2200mm
Input Power AC: 380/400/415Vac, 50/60Hz (optional DC: 240/336Vdc)
refrigerant R410A
Fluorine pump Optional
Chilled water air conditioner Cooling capacity 12kW~70kW
Internal size 300/600×1000/1100/1200×2000/2200mm
Input Power AC: 380/400/415Vac, 50/60Hz (optional DC: 240/336Vdc)
refrigerant Water/ethylene glycol aqueous solution
Integrated UPS (UPS built-in) Input voltage 380/400/415VaC,50/60Hz,3Ph+N+PE
Input power factor Full load>0.99, half load>0.98
Rated capacity 50~200KVA
Overall efficiency ≥96%
AC lightning protection B and C grades
Modular power distribution cabinet (UPS external) Input voltage 380/400/415VaC,50/60Hz,3Ph+N+PE
Rated capacity 500A
AC lightning protection B and C grades