Configuration |
Parameters |
Overall system parameters |
Number of cabinets supported by a single module |
1-12 cabinets |
Maximum available space |
420U (12 cabinets, excluding battery pack, load 54kW) |
Channel Type |
Single-row channel, natural heat dissipation/enclosed cold channel/enclosed hot and cold channel |
Power density range |
3-8kW/cabinet |
Battery deployment method |
Battery packs, battery cabinets, battery racks |
Battery backup time |
15min-240min |
Installation |
Concrete floor, raised floor |
Power supply type |
Single-phase three-wire/three-phase five-wire |
System protection level |
IP20 (mesh door) / IP50 (glass door) |
Operating temperature |
-20C-45℃ |
altitude |
If the distance exceeds 1000m, the rating needs to be reduced. |
Cabinet System |
Natural cooling |
(N*600)*1200*2000mm, excluding casters and adjustable feet, front and rear high-density ventilation mesh doors, n is the number of cabinets |
Closed Cold Aisles |
(N*600)*1200*2000mm, excluding casters and adjustable feet, front glass door, rear mesh door, n is the number of cabinets |
Closed hot and cold aisles |
(N*600)*1400*2000mm, excluding casters and adjustable feet, front and rear glass doors. n is the number of cabinets |
IP Rating |
IP20 (mesh door) / IP50 (glass door) |
Refrigeration system |
Input Power |
220Vac |
Cooling capacity (single air conditioner) |
4.5kW(4U)/8kW(10U)/15kW(12U)/30kW(21U) |
Air conditioning configuration |
1+0, 1+1, 2+0, 2+1, 3+0, 3+1 (optional) |
Sensible heat ratio (sensible cooling capacity/total cooling capacity) |
1 |
refrigerant |
R410A |
Air supply method |
Front air supply, rear air return |
Installation |
Rack Mount |
Power supply and distribution system |
Power Input |
Single-phase three-wire/three-phase five-wire |
UPS capacity |
3kVA/6kVA/10kVA/20kVA |
UPS Configuration |
N, N+1 |
UPS rated input voltage |
220Vac/230Vac/240Vac single phase; 380Vac/400Vac/415Vac three phase |
UPS input voltage range |
80Vac~280Vac single phase: 138Vac~485Vac three phase |
UPS output power factor |
0.8/0.9 |
UPS rated output voltage |
220Vac/230Vac/240Vac single phase; 380Vac/400Vac/415Vac three phase |
UPS overall efficiency |
92%/95% |
Maintenance bypass |
support |
Number of mains feed-out channels |
4-way IT + 4-way air conditioning and fire protection / 12-way IT + 5-way air conditioning and fire protection |
UPS feed-out number |
4-way IT/12-way IT |
AC lightning protection |
B and C grades |
Monitoring system |
Monitoring system host |
Support embedded Web direct access |
Local interface |
10.1 inch industrial touch panel |
Leaking Rope |
Standard |
Smoke |
Standard |
Temperature and humidity |
Standard |
Automatic door opening device |
Optional |
Door sensor |
Optional |
Power supply/UPS/air conditioning monitoring |
Standard |
Northbound communication interface |
Optional |
Protocol Format |
SNMP |
SMS alarm |
Optional |
Emergency fan |
Optional |
Cabinet light strip |
Standard |
Fire protection system |
Heptafluoropropane gas fire fighting module |
1U rack-mount installation, single module can manage two cabinets (optional) |